4.10 Mixed inlet-outlet condition
The inlet-outlet boundary condition is the
most basic example of the mixed fixed value/gradient type, described
in Sec. 4.9
. The condition sets the reference
gradient and uses a specified reference value
. The value fraction is
then set to
![]() |
(4.11) |

![]() |
(4.12) |

The figure shows the solution of
Eq. (2.65
),
converged over time with and unity Prandtl number
, see
Sec. 2.21
. The fixed condition
is
applied at the inlet and a zero gradient condition
at the walls.
At the free boundary, the inlet-outlet condition
enables to be specified where inflow occurs. The inlet value in the
example is set to
; the image shows mixing of fluids at different
temperatures, from the inlet and entrained at the free boundary.
Numerical benefit of inlet-outlet
Boundaries may be described “inlet” and “outlet” based on the expectation of the flow direction during a simulation. But the flow direction may not always happen as expected.
In the case of an outlet, for example, inflow might occur during a simulation. For example, at the start of a simulation, the initial conditions may induce inflow before the internal flow is established. Localised inflow can also occur when rotating flow structures pass through an outlet boundary, e.g. when a bluff body sheds vortices, as shown below.
Where inflow occurs, the inlet-outlet condition
can switch to the fixed value type to ensure stability, as discussed
in Sec. 4.5
. The inlet-outlet
condition is therefore commonly applied to scalar fields (except
),
at a boundary which is notionally an outlet, to avoid numerical
instability associated with unexpected inflow.